Home Categories Send inquiry

GT-AEC2331a Industrial and commercial combustible gas detector

Technical Parameters

Item

Data

Detected gases

Natural gas

Principle of detection

Catalytic combustion

Sampling mode

Diffusive sampling

Range

3-100%LEL

Operating voltage

DC24±6V

Power consumption

≤1W (DC24V)

Electrical interface

NPT3/4"

Protection grade

IP66

Explosion proof grade

ExdⅡCT6Gb

Shell

Cast aluminum

Dimension

Length × width × thickness: 110mm×103mm×55mm

Weight

About 530g

Major Features

High intelligence and digitalization

High-performance micro-controller technology, automatic failure identification and automatic alarm, high-concentration gas over limit protection;

Only one ESN. No code dialing is required, reducing the complexity of manual code dialing;

Sensitivity curve attenuation compensation

Advanced embedded software treatment technology, automatic service life attenuation compensation and high sensitivity;

Real-time concentration detection

Real-time gas concentration detection; concentration information is transmitted to an adaptive controller;

Portable and small size, easy to mount

The product is portable and small in size, applicable to diversified mounting modes and easy to mount.

Model Selection

Model

Signal output

Sensor equipped

Adaptive control system

GT- AEC2331a

Four-bus communication

(S1, S2, GND and +24V)

Catalytic combustion

ACTION gas alarm controllers:

AEC2301a, AEC2302a, AEC2303a and AEC2305

Detector Structure

1. Install bottom board
2. Bottom box
3. Explosion-proof single-sealed cable gland
4. M4 x10 Hexagon socket head cap screw
5. Sensor cover
6. Light guide
7. Top cover

Detector Structure

A. Holding pipe-mounted (Holding pipe diameter DN20)

B. Vertical pipe-mounted (Holding pipe diameter DN20)

C. Wall-mounted

D. Ceiling-mounted


GT-AEC2331a Industrial and commercial combustible gas detector Related Video: